Mortuary refrigeratorsMortuary refrigerators 2022. 12. 31. 12:38
Fabrication Specification for Mortuary Refrigerators of Busung Freezer Industrial Co., Ltd.
1. Mortuary refrigerators system components
1-1 Panel part
1) Urethane panel
2) Vat
3) Door
4) Caster
1-2 All-in-one refrigerator power 220V 60Hz(220V 50Hz) 0.5kw (refrigerant R-134a, R-404)
1) Casing
2) Condenser
3) Hermetic compressor 1/3HP (Compressor)
4) Fan for condenser
5) Control box and operation panel
6) Evaporator
7) Fan for evaporator
8) Refrigerant piping
9) Refrigerant pipe insulation
10) Protective device
11) Defrost water evaporator
12) Other
1-3 Automatic control
1) Alarm and status display
1-4 Using Temperature range
1) 0 ℃ to 10 ℃ for Mortuary refrigerator (For user’s convenience, set at 4℃ on the time of ex-factory)
2) If it is required for the user to operate at the temperature under -10 ℃ to - 20 ℃,
please use a Mortuary freezer. (For user’s convenience, set at -15℃ on the time of ex-factory)
2. Material and feature
2-1 Panel part
1) Non-corrosive stainless steel (internal: 2B 0.6t, external: 2B H/L 0.6t) is used and each of the
component parts must be manufactured according to the intended use, and sufficient mechanical
strength and feature made to apply
2) It should be installed easily both indoors and outdoors, and should be manufactured for the
maintenance in convenience.
3) It should be used the panel with over 50 mm of thickness of urethane foam which can minimize
heat transfer
4) It should be foamed not to get a foreign substance stuck in the corner between the lower panel
and upper panel (refer to the attached figure)
This makes it convenient assembling or disassembling for the side panel, the upper and lower panels
so as to maintain airtightness.
5) It should be attached an overheat prevention heater at the door frame of the refrigerator to prevent
overheating and heat rays. It should be prevented from the dew condensation through no temperature
difference with the outside.
6) Door locks and fixing hinges must be manufactured to withstand the load. Must be stainless or chrome
plated.
7) Handle and hinge fixing bracket (3.2T burring tap) is used to prevent corrosion. It must be galvanized.
8) It should be attached the caster (swivel and fixing) and high poles at the lower side of refrigerator so as
to install the refrigerator and move in convenience.
9) As for the panel dedicated to the infected, it is sealed between the upper and the lower compartments,
and operates independently.
2-2 All-in-one refrigerator
1) Casing
- The material is used 1.2T of electric galvanized steel sheet (EGI) which has mechanical feature,
hardness, flexure, shape, dimension and thickness. These are in accordance with KSD 3528
- The coating method is spray coating with a coating film thickness of 20μ ±1 using powder coating. Dry for
20 minutes at a temperature of 130 ℃.
- The standard color is ivory.
- It should be easy assembling structure. In case of A/S, it should be manufactured easy disassembling for
the repairing in convenience.
2) Condenser
- The thermocouple must be a seamless phosphorus deoxidized copper tube (KSD 5301) or equivalent
with a purity of 99% or higher, and there should be the uniformity of the copper tube and no harmful
have sufficient thermal contact surface.
- It uses the FIN which is 0.11T of Aluminum foil with a purity of 99.9% or more.
It should be coated with thermosetting resin on FIN in order to improve excellent corrosion resistance and
thermal efficiency.
- It should be implemented for the pressure test at 37.5kg/cm2.G, and the airtight test at a pressure of
25kg/cm2.G or above. There should be no abnormalities such as leakage and deformation.
3) Hermetic reciprocating compressor (Compressor)
- The compressor is an internationally verified hermetic compressor.
- Use alternative refrigerants R-134 and R-404 for refrigerant.
- When connecting the compressor with pipe, the welding area is
coated with an anticorrosion paint, and wiring use a contactor.
- To protect the winding of the compressor motor, it is used the Compressor
coverload relay F.O.C.R or the overload protector MPDULE to prevent from the damage to the motor.
- When assembling the compressor with the base, vibration-proof rubber and vibration-proof spring are
used to prevent from the vibration.
- It is installed a CHARGE NIPPLE on the compressor for refrigerant supplement and air tightness test.
- Make sure to drive the compressor at about 70% of the maximum load.
4) Fan for condenser
- Make sure to use a fan with a low-noise propeller type, and it should be able to blow a sufficient air for
condensation.
- It has sufficient strength for the required RPM, and performs static and dynamic balance tests for a quiet
operation.
- The motor is insulation class F, and its structure and general characteristics are in accordance with KSC
4201~4206 conformity.
- The drive method is a direct connection method.
5) Control box and operation panel
- Make it possible to display various operating conditions of the device. (run/stop, defrost timer switch,
temperature controller, thermometer and various indicators)
- All parts should have no abnormality in the withstand voltage test.
6) Evaporator
- The thermocouple must be a seamless phosphorus deoxidized copper tube (KSD 5301) or equivalent
with a purity of 99% or higher, and there should be the uniformity of the copper tube and no harmful
defects in use.
- As for the copper tube and the FIN, these are mechanically expanded and closely contacted so that they
have sufficient thermal contact surface.
- It uses the FIN which is 0.11T of Aluminum foil with a purity of 99.9% or higher. It should be coated with
thermosetting resin on FIN in order to improve excellent corrosion resistance and thermal efficiency.
- It should be implemented for the pressure test at 22kg/cm2.G, and the airtight test at a pressure of
15kg/cm2.G or above. There should be no abnormalities such as leakage and deformation.
7) Fan for Evaporator
- Make sure to use a fan with a low-noise propeller type, and it should be able to blow a sufficient air for
condensation.
- It has sufficient strength for the required RPM, and performs static and dynamic balance tests for a
quiet operation.
- The motor is insulation class F, and its structure and general characteristics are in accordance with
KSC 4201~4206 conformity.
- The drive method is a direct connection method.
8) Piping for Refrigerant
- For the thermocouple, use a non-seamless phosphorus deoxidized copper tube (KSD 5301) with a purity
over 99% or equivalent one, and there should be uniformity of the copper tube and no harmful defects in
use.
- Make sure to be minimized bends during piping work.
- After the piping is installed, perform a leak test with nitrogen gas to confirm no abnormality.
9) Insulation for Refrigerant pipe
- Insulation of the pipe is made as the same size as the copper pipe.
- Make sure that there are no cracks in the seam of the insulation material.
- Insulation is carried out by wrapping with primary vinyl, insulating secondary, and applying maximum
pressure with the tape for cooler. (Pipe is applied when installing outdoor unit)
10) Protection device
- Over current relay, Module, Fusible plug, Fuse
- Expansion valve
- Use a thermostatic expansion valve or capillary tube (2.2~2.6mm).
- When using a thermosensitive type, be careful about the sensing point.
- When using a capillary tube, wind it using a 50mm tube and install it.
- Insert the capillary tube sufficiently into the pipe to avoid clogging the welding area before welding.
11) Defrost water evaporator
- Create a clean and hygienic environment by installing a forced or automatic evaporator
12) Scope of supply
- Supplier Assembling the mortuary refrigerator Trial run
- User
Foundation work
Primary side electrical wiring work
Installation of sewage facilities and trenches to allow drainage during floor clean
Body Mortuary refrigerator (Body cabinet, Body refrigerator, Body freezer, Morgue refrigerator, Morgue freezer, Mortuary freezer, Mortuary refrigerators) installation and connecting to 4 units
SejongB/D 4F, #229-8, Kuui-Dong, Kwangjin-Ku, Seoul 143-823 Korea
Tel : (822) 3437-8661 Fax : (822) 3436-6711 E-mail : sseon2010@hanmail.net
Mobile phone : 82-10-6410-7577 Manufacture plant E-mail : j84416@gmail.com